RCBO Size Chart: Standard Ratings and Sizing Guide

An RCBO size chart helps you choose the correct residual current circuit breaker with overcurrent protection for an electrical circuit. RCBOs combine the functions of an MCB and RCD, providing protection against overload, short circuits, and residual-current or earth-leakage faults.

Common RCBO ratings include 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, and 63A. However, the correct rating depends on the circuit load, conductor size, installation method, voltage, fault conditions, and applicable electrical standards.


What Is an RCBO?

An RCBO (Residual Current Circuit Breaker with Overcurrent protection) is a protective switching device designed to provide two major types of electrical protection in one unit.

It combines:

  • Overload protection
  • Short-circuit protection
  • Residual-current protection
  • Earth-leakage protection
  • Circuit isolation, depending on the device design

Unlike a conventional RCD, an RCBO also protects the circuit from excessive current. This makes it particularly useful for protecting individual lighting, socket, appliance, and dedicated equipment circuits.

The RCBO rating is normally expressed in amperes (A). For example, a 16A RCBO is designed for a circuit with a rated current of 16 amperes.


RCBO Size Chart

The following chart shows common RCBO current ratings and typical circuit applications. These applications are general examples rather than universal rules because the required breaker rating must be determined from the actual circuit design.

RCBO Size Typical Circuit Use Approximate Single-Phase Load at 230V
6A Small lighting and control circuits 1.38 kW
10A Lighting and small appliances 2.30 kW
16A Lighting, sockets, small appliances 3.68 kW
20A Socket and dedicated appliance circuits 4.60 kW
25A Larger appliances and dedicated circuits 5.75 kW
32A Heaters, cookers, air conditioners, larger loads 7.36 kW
40A High-load dedicated circuits 9.20 kW
50A Larger appliances and subcircuits 11.50 kW
63A Feeders and high-current circuits 14.49 kW

The load figures are calculated using Power = Voltage × Current at 230V and represent a simple theoretical maximum. They should not be treated as the permitted continuous load for a particular installation.

Different RCBO product ranges may offer additional ratings, including smaller ratings and ratings above 63A.


Understanding RCBO Ampere Ratings

The number printed on an RCBO indicates its rated current (In).

For example:

  • B6 = 6A RCBO with B-curve overcurrent protection
  • B10 = 10A RCBO
  • B16 = 16A RCBO
  • B20 = 20A RCBO
  • B32 = 32A RCBO
  • C32 = 32A RCBO with C-curve characteristics

The ampere rating should never be selected simply because it matches the appliance’s maximum possible power. The breaker must also coordinate with the cable ampacity and installation conditions.


Common RCBO Sizes and Applications

6A RCBO

A 6A RCBO is commonly considered for low-current circuits such as small lighting, control, signaling, and similar loads.

It may be suitable where the calculated circuit current is comfortably below the device rating and the connected wiring is appropriately protected.

10A RCBO

A 10A RCBO is often used for relatively small electrical circuits.

Typical examples can include:

  • Lighting circuits
  • Small fixed equipment
  • Control circuits
  • Low-power appliances

The actual application depends on local wiring practices and circuit design.

16A RCBO

A 16A RCBO is one of the common ratings used in many IEC-style electrical installations.

It may be used for:

  • Socket circuits
  • Lighting circuits
  • Small appliances
  • Dedicated equipment

A 16A rating does not automatically mean every circuit using a particular cable size can use a 16A breaker. Cable installation conditions still need to be checked.

20A RCBO

A 20A RCBO is suitable for circuits designed to carry higher current than a typical 16A circuit.

Potential applications include:

  • Dedicated appliances
  • Socket circuits
  • Small heaters
  • Equipment circuits

The connected load and conductor capacity should be checked before selecting the breaker.

25A RCBO

A 25A RCBO is commonly considered for dedicated medium-load circuits.

Applications may include:

  • Heating equipment
  • Larger appliances
  • Dedicated machinery
  • Small air-conditioning equipment

The actual breaker size should be based on the calculated design current and cable protection requirements.

32A RCBO

A 32A RCBO is widely used for higher-load final circuits.

Possible applications include:

  • Electric heaters
  • Cooking equipment
  • Air-conditioning units
  • Larger appliances
  • Dedicated power circuits

Motors and compressor-based equipment may require special consideration because their starting current can affect the choice of trip curve.

40A, 50A, and 63A RCBOs

Higher-rated RCBOs are generally used for larger dedicated circuits, distribution circuits, or equipment with higher electrical demand.

A 63A RCBO, for example, has a rated current of 63A, but that does not mean it should simply be installed whenever the calculated load approaches 63A. Cable capacity, voltage drop, fault protection, and device coordination must all be considered.


RCBO Size by Load Current

One of the first steps in selecting an RCBO is determining the circuit’s design current.

For a simple single-phase resistive load:

Current = Power ÷ Voltage

For example, a 3,000W load on a 230V supply has a theoretical current of:

3,000 ÷ 230 ≈ 13.0A

A suitable protective-device rating cannot be selected from this calculation alone. The cable rating, installation method, continuous-load requirements, temperature, grouping, and applicable code must also be considered.

For motors and other equipment, power factor and efficiency may also affect the calculation.


RCBO Size Chart by Common Load Range

The following table can be used as a planning reference, not as a substitute for circuit design calculations.

Approximate Design Current RCBO Rating to Evaluate Example Applications
Up to 6A 6A Small lighting/control circuits
Up to 10A 10A Lighting, small equipment
Up to 16A 16A Sockets, small appliances
Up to 20A 20A Dedicated appliances
Up to 25A 25A Medium-load equipment
Up to 32A 32A Heating, larger appliances
Up to 40A 40A High-load equipment
Up to 50A 50A Large dedicated circuits
Up to 63A 63A High-current circuits

The protective device must be coordinated with the conductor and the installation rather than selected solely from this table.


RCBO B Curve vs C Curve

The trip curve is another important part of RCBO selection.

B Curve RCBO

A B-curve RCBO generally has an instantaneous magnetic trip range of approximately 3–5 times its rated current.

B-curve devices are commonly considered for circuits with relatively low starting or inrush currents.

Typical applications include:

  • Lighting
  • General sockets
  • Resistive loads
  • Small appliances

C Curve RCBO

A C-curve RCBO generally has an instantaneous magnetic trip range of approximately 5–10 times its rated current.

It may be more appropriate for equipment with higher temporary starting currents, such as:

  • Motors
  • Pumps
  • Compressors
  • Some air-conditioning equipment
  • Certain power tools

The curve should be selected based on the equipment and installation characteristics rather than simply choosing C-curve because it is “stronger.”


What Does 30mA Mean on an RCBO?

A common RCBO marking is 30mA.

This refers to the device’s rated residual operating current (IΔn), not its load-current rating.

For example:

B16 30mA RCBO

means:

  • B = overcurrent trip characteristic
  • 16A = rated current
  • 30mA = residual-current operating sensitivity

The 30mA function is commonly used where additional protection against electric shock is required, subject to the applicable electrical regulations.

Other residual-current ratings, such as 10mA, 100mA, 300mA, may be available for specific applications.


Type AC vs Type A RCBO

RCBOs can have different residual-current sensing characteristics.

Type AC

Type AC devices are designed to detect sinusoidal AC residual currents.

Type A

Type A devices can detect AC residual current as well as certain pulsating DC residual currents.

This can make Type A protection appropriate for many modern circuits containing electronic equipment.

Potential applications include circuits supplying:

  • LED drivers
  • Electronic power supplies
  • Computers
  • Washing machines
  • Modern appliances
  • Power electronics

Always select the residual-current type according to the equipment and applicable requirements.

Discover More:


RCBO Pole Configuration

RCBOs are available in different pole configurations.

Common configurations include:

  • 1P+N
  • 2P
  • 3P
  • 3P+N
  • 4P

A 1P+N RCBO is commonly used for single-phase circuits where the phase and neutral are accommodated according to the device design.

Three-phase installations may require multi-pole RCBOs.

The pole arrangement must match the electrical system, consumer unit or distribution board, and manufacturer’s specifications.


RCBO Breaking Capacity

Another important specification is the breaking capacity.

Common ratings include:

  • 4.5kA
  • 6kA
  • 10kA

Breaking capacity indicates the prospective fault current that the device is designed to interrupt under its specified conditions.

A higher ampere rating does not automatically mean a higher breaking capacity.

For example, a 32A 6kA RCBO and a 32A 10kA RCBO have the same rated current but different short-circuit interruption capabilities.

The required breaking capacity must be appropriate for the prospective short-circuit current at the installation point.


RCBO Size and Wire Size

Choosing an RCBO requires coordination between the protective device and conductor.

A simplified planning relationship is:

Load current ≤ RCBO rating ≤ allowable conductor capacity

However, real installations are more complicated because conductor ampacity can change according to:

  • Conductor material
  • Cable insulation
  • Ambient temperature
  • Number of loaded conductors
  • Grouping
  • Installation method
  • Raceway or conduit conditions
  • Cable length
  • Voltage drop
  • Local electrical regulations

Therefore, there is no universal table saying that one particular wire size always requires one specific RCBO.


How to Choose the Correct RCBO Size

Follow these steps when selecting an RCBO.

1. Calculate the Load Current

Determine the expected operating current of the circuit.

For a basic single-phase load:

I = P ÷ V

For a three-phase load, the calculation may involve voltage, power factor, and efficiency.

2. Determine the Cable Size

Select a conductor that can safely carry the design current under the actual installation conditions.

3. Select the RCBO Rating

Choose an RCBO that provides suitable overload protection for the circuit conductor and load.

4. Check the Trip Curve

Choose B, C, or another appropriate characteristic according to the type of load and expected starting current.

5. Select Residual-Current Sensitivity

Determine whether the circuit requires 30mA or another residual-current rating.

6. Check Breaking Capacity

Confirm that the RCBO’s short-circuit rating is adequate for the installation.

7. Verify Compatibility

The RCBO must physically and electrically match the distribution board or consumer unit.

Discover More:


RCBO vs MCB vs RCD

Understanding the difference between these devices makes RCBO selection easier.

Device Overload Protection Short-Circuit Protection Residual-Current Protection
MCB Yes Yes No
RCD/RCCB No No* Yes
RCBO Yes Yes Yes

*An RCD generally requires suitable overcurrent protection upstream.

The major advantage of an RCBO is that it combines multiple protection functions into one circuit-level device.


Advantages of Using an RCBO

RCBOs offer several practical advantages in modern electrical installations.

  • Individual circuit protection
  • Combines MCB and RCD functions
  • Helps limit nuisance shutdowns to the affected circuit
  • Provides overload protection
  • Provides short-circuit protection
  • Provides residual-current protection
  • Can save distribution-board space depending on the design
  • Makes circuit-level protection easier to organize

A fault on one RCBO-protected circuit does not necessarily disconnect every other circuit in the installation.


Common RCBO Selection Mistakes

Several mistakes can result in poor circuit protection.

Choosing the RCBO Only by Load

A circuit drawing 20A does not automatically mean a 20A RCBO is correct. The cable and installation conditions must also be checked.

Ignoring the Trip Curve

A motor can have significant starting current. Using an unsuitable curve may cause nuisance tripping.

Ignoring Breaking Capacity

The RCBO must be capable of interrupting the prospective fault current where it is installed.

Confusing 30mA With Ampere Rating

A 30mA marking relates to residual-current protection. It does not mean the RCBO is rated at 0.03A for normal load current.

Using an Incompatible RCBO

RCBOs are not necessarily interchangeable between every consumer unit or distribution board. Physical mounting, busbar arrangement, terminal configuration, and manufacturer compatibility can matter.

Oversizing the RCBO

Installing a larger breaker to prevent nuisance tripping can leave the conductor inadequately protected.

Discover More:


RCBO Size Chart Quick Reference

RCBO Rating Common General Use
6A Small lighting/control circuits
10A Lighting and low-power circuits
16A Sockets and small appliances
20A Medium-load circuits
25A Dedicated appliance circuits
32A Larger appliances and heating
40A High-load dedicated circuits
50A Larger equipment circuits
63A High-current feeders/circuits

This is a general reference chart, not a substitute for electrical design calculations or local code requirements.


Frequently Asked Questions

What are the common RCBO sizes?

Common RCBO ratings include 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, and 63A. Some manufacturers also produce smaller or larger ratings. The correct size depends on the circuit design, cable capacity, load current, and applicable electrical requirements.

What size RCBO do I need for a 16A load?

A 16A load may require a 16A RCBO, but this cannot be determined from load current alone. The conductor rating, installation method, voltage drop, temperature, grouping, fault conditions, and local electrical requirements should also be checked before selecting the protective device.

What does 30mA mean on an RCBO?

The 30mA rating refers to the RCBO’s residual-current operating sensitivity. It is associated with earth-leakage protection rather than the normal circuit load rating. A device marked 16A 30mA is rated for 16A load current and has 30mA residual-current sensitivity.

Is a B-curve or C-curve RCBO better?

Neither is universally better. A B-curve RCBO is commonly suitable for circuits with low inrush current, while a C-curve RCBO may be appropriate for loads with higher starting currents, such as motors. The correct curve depends on the equipment and circuit characteristics.

Can an RCBO replace an MCB and RCD?

An RCBO can combine the overcurrent protection normally provided by an MCB with residual-current protection normally provided by an RCD. However, the specific device must be suitable for the installation, distribution board, earthing arrangement, and applicable electrical requirements.


Conclusion

An RCBO size chart is useful for quickly comparing common ratings from 6A through 63A, but selecting the correct RCBO involves more than matching the breaker rating to the appliance load.

You should consider the design current, cable size, installation method, trip curve, residual-current sensitivity, breaking capacity, pole configuration, and applicable electrical standards.

For reliable protection, the RCBO should be properly coordinated with the circuit conductor and equipment. When the installation conditions are uncertain, the final selection should be verified by a qualified electrical professional.