Armored Cable Size Chart: Find the Right Cable Size

An armored cable size chart helps you compare common cable conductor sizes and understand where different armored cables may be used. Armored cables are designed to provide electrical power while adding mechanical protection through a metallic armor layer.

Common armored cable sizes range from 1.5 mm² to 630 mm², although the available sizes depend on the cable type, conductor material, voltage rating, number of cores, insulation, and manufacturer.

Choosing the correct armored cable involves more than selecting a conductor cross-sectional area. Current-carrying capacity, voltage drop, short-circuit withstand, installation method, cable length, ambient temperature, grouping, mechanical protection, and termination requirements should all be considered.


What Is Armored Cable?

An armored cable is an electrical cable containing a protective metallic layer around the insulated conductors.

The armor provides additional protection against:

  • Mechanical impact
  • Crushing
  • Abrasion
  • Installation damage
  • Certain environmental conditions
  • Rodent damage in appropriate applications

Depending on the cable construction, the armor may also have an electrical bonding or earthing function.

Common armored cable constructions include steel wire armored (SWA), aluminum wire armored (AWA), and steel tape armored designs.

Armored cables are widely used for power distribution, industrial equipment, underground installations, outdoor systems, commercial buildings, and other demanding applications.


Armored Cable Size Chart

The following table provides a general reference for common armored cable conductor sizes.

Cable Size Typical Conductor Material Common Applications
1.5 mm² Copper / Aluminum Small lighting and control circuits
2.5 mm² Copper / Aluminum Small power and socket circuits
4 mm² Copper / Aluminum Medium power circuits
6 mm² Copper / Aluminum Larger branch circuits
10 mm² Copper / Aluminum Small feeders and equipment
16 mm² Copper / Aluminum Distribution and equipment
25 mm² Copper / Aluminum Medium feeders
35 mm² Copper / Aluminum Distribution systems
50 mm² Copper / Aluminum Larger feeders
70 mm² Copper / Aluminum High-current distribution
95 mm² Copper / Aluminum Industrial feeders
120 mm² Copper / Aluminum Large power distribution
150 mm² Copper / Aluminum High-load feeders
185 mm² Copper / Aluminum Industrial distribution
240 mm² Copper / Aluminum Large power systems
300 mm² Copper / Aluminum High-capacity feeders
400 mm² Copper / Aluminum Heavy power distribution
500 mm² Copper / Aluminum Large industrial systems
630 mm² Copper / Aluminum Very high-current systems

These are conductor cross-sectional areas, not the overall diameter of the finished armored cable.

The actual cable diameter, weight, current capacity, and construction can vary substantially between manufacturers.


Understanding Armored Cable Sizes

Armored cable size is normally expressed using the conductor’s cross-sectional area in square millimeters (mm²).

For example:

  • 4 mm²
  • 10 mm²
  • 25 mm²
  • 70 mm²
  • 120 mm²
  • 240 mm²

A larger mm² value generally means a larger conductor capable of carrying more current, subject to installation conditions.

However, cable size does not directly indicate:

  • Overall cable diameter
  • Armor thickness
  • Cable weight
  • Number of cores
  • Insulation thickness
  • Current capacity under every installation condition

For this reason, two cables with the same conductor size can have different outside dimensions.


Armored Cable Core Configurations

Armored power cables are available in different core configurations.

Common options include:

  • 1-core
  • 2-core
  • 3-core
  • 4-core
  • 5-core

The correct configuration depends on the electrical system and application.

1-Core Armored Cable

Single-core armored cables are often used for high-current power transmission and specialized distribution applications.

For AC systems, the armor arrangement and magnetic effects require particular attention. Aluminum armor or other appropriate constructions may be used depending on the design.

2-Core Armored Cable

Two-core cables may be used for certain single-phase power systems where separate conductors are required for the circuit.

3-Core Armored Cable

Three-core cables are commonly used in three-phase systems where a neutral conductor is not required within the cable.

4-Core Armored Cable

Four-core armored cables can be used in three-phase systems where three phase conductors and a neutral are required.

5-Core Armored Cable

Five-core cables are commonly used where three phases, neutral, and protective earth or grounding conductors are required within the cable arrangement, depending on the system design.


SWA Cable Size Chart

Steel Wire Armored (SWA) cable is one of the most recognized types of armored power cable.

Common conductor sizes include:

SWA Conductor Size Typical Use
1.5 mm² Small power and lighting
2.5 mm² General power
4 mm² Medium circuits
6 mm² Larger branch circuits
10 mm² Small feeders
16 mm² Distribution
25 mm² Medium feeders
35 mm² Power distribution
50 mm² Larger feeders
70 mm² High-current circuits
95 mm² Industrial feeders
120 mm² Large distribution
150–240 mm² High-load systems
300–630 mm² Heavy industrial distribution

The correct SWA cable depends on the load, installation method, voltage, cable length, and other design conditions.


Armored Cable Current Capacity

The current-carrying capacity, or ampacity, is one of the most important factors when selecting an armored cable.

However, there is no single current rating that applies to every cable size.

Ampacity depends on:

  • Conductor material
  • Cable insulation
  • Number of cores
  • Number of loaded conductors
  • Installation method
  • Ambient temperature
  • Soil thermal conditions for buried cable
  • Cable grouping
  • Cable spacing
  • Surrounding thermal environment
  • Armor construction
  • Voltage level

Therefore, an armored cable ampacity chart should always be associated with a specific cable construction and installation method.


Armored Cable Size by Approximate Current

The following table is intended only as a general planning reference.

Approximate Design Current Cable Sizes to Evaluate
Up to 15A 1.5–2.5 mm²
Up to 25A 2.5–4 mm²
Up to 35A 4–6 mm²
Up to 50A 6–10 mm²
Up to 70A 10–16 mm²
Up to 100A 16–25 mm²
Up to 125A 25–35 mm²
Up to 160A 35–50 mm²
Up to 200A 50–70 mm²
Up to 250A 70–95 mm²
Up to 315A 95–150 mm²
Up to 400A 150–240 mm²

These ranges are not universal ampacity ratings. They are starting points for evaluation. The final cable size should be selected using the actual cable manufacturer’s data and applicable electrical requirements.

Discover More:


Copper vs Aluminum Armored Cable

Armored cables can use either copper or aluminum conductors.

Copper Armored Cable

Copper offers:

  • High electrical conductivity
  • Good mechanical strength
  • Compact conductor dimensions
  • Excellent termination characteristics

Copper cables are often preferred where space is limited or where their mechanical and electrical properties provide an advantage.

Aluminum Armored Cable

Aluminum generally offers:

  • Lower conductor weight
  • Lower material cost in many applications
  • Larger conductor dimensions for equivalent resistance compared with copper

Aluminum can be a practical choice for larger feeders and distribution systems where weight and cost are important considerations.

The terminals and connectors must be suitable for the conductor material.


XLPE vs PVC Armored Cable

Armored cables are available with different insulation materials.

PVC Armored Cable

PVC-insulated cables are widely used for general power distribution and many conventional electrical installations.

Advantages can include:

  • Cost effectiveness
  • Good general insulation
  • Easy availability
  • Wide range of sizes

XLPE Armored Cable

XLPE (cross-linked polyethylene) insulation can provide higher conductor operating temperature capability than many PVC designs.

XLPE cables are commonly considered for:

  • Higher-load applications
  • Industrial power systems
  • Underground distribution
  • Larger feeders
  • Applications requiring greater thermal performance

The actual temperature rating must always be confirmed from the cable specification.


SWA vs AWA Cable

The armor material is an important consideration.

SWA — Steel Wire Armor

SWA is commonly used for:

  • Multicore power cables
  • Underground power distribution
  • Industrial installations
  • Building power systems

Steel provides strong mechanical protection.

AWA — Aluminum Wire Armor

Aluminum Wire Armor (AWA) is commonly used in certain single-core AC cable applications.

A key reason for selecting aluminum armor in these applications is to reduce magnetic effects associated with ferromagnetic armor around a single AC conductor.

The cable design should be selected according to the electrical system and manufacturer’s specifications.

Discover More:


Armored Cable Voltage Drop

Voltage drop becomes increasingly important as cable length increases.

A cable can have sufficient current-carrying capacity while still producing excessive voltage drop over a long distance.

Voltage drop depends on:

  • Cable length
  • Load current
  • Conductor resistance
  • Conductor material
  • Power factor
  • Number of phases
  • Cable arrangement
  • Operating temperature

For long cable runs, you may need to select a larger conductor size than the minimum required for ampacity.

For three-phase systems, voltage-drop calculations commonly involve the relationship between current, cable impedance, length, and phase voltage.


Armored Cable for Underground Installation

Armored cable is often used underground because its protective armor can improve resistance to mechanical damage.

However, underground cable selection requires consideration of:

  • Burial depth
  • Soil thermal resistivity
  • Ground temperature
  • Water and moisture
  • Cable grouping
  • Mechanical protection
  • Warning systems
  • Cable spacing
  • Voltage drop

Direct burial suitability should be confirmed from the cable’s construction and installation requirements.

Armor does not automatically make every cable suitable for direct burial.


Armored Cable for Outdoor Applications

Outdoor installations expose cables to environmental conditions such as:

  • Sunlight
  • Rain
  • Moisture
  • Temperature changes
  • Physical impact
  • Chemicals
  • UV radiation

The complete cable construction should therefore be appropriate for the environment.

The outer sheath, armor, insulation, glands, joints, and terminations all contribute to the overall installation performance.


Armored Cable Glands and Terminations

Selecting the correct cable is only part of an armored cable installation.

The cable also requires appropriate glands, lugs, terminals, cleats, and accessories.

Cable gland selection can depend on:

  • Cable overall diameter
  • Armor type
  • Number of cores
  • Cable size
  • Indoor or outdoor installation
  • Enclosure type
  • Environmental protection requirements

The gland must be compatible with the specific cable construction.

Incorrect gland selection can compromise mechanical retention, environmental sealing, and electrical continuity.


Armored Cable Size and Cable Diameter

Cable size in mm² should not be confused with overall cable diameter.

For example, a 25 mm² armored cable may have a considerably different outside diameter depending on whether it is:

  • 2-core
  • 3-core
  • 4-core
  • Copper
  • Aluminum
  • PVC insulated
  • XLPE insulated
  • SWA
  • AWA

Therefore, always use the manufacturer’s dimensional data when planning:

  • Cable glands
  • Conduit entries
  • Trunking
  • Cable trays
  • Ducts
  • Cable cleats
  • Panel entries

How to Select the Correct Armored Cable Size

1. Determine the Load

Calculate the expected design current.

For a basic single-phase load:

I = P ÷ V

For a three-phase load:

I = P ÷ (√3 × V × PF × η)

where power factor and efficiency should be included when applicable.

2. Select the Number of Cores

Determine whether the system requires:

  • 1 core
  • 2 cores
  • 3 cores
  • 4 cores
  • 5 cores

3. Choose Conductor Material

Compare copper and aluminum based on electrical performance, installation requirements, weight, cost, and termination compatibility.

4. Check Ampacity

Verify that the selected cable can safely carry the design current under the actual installation conditions.

5. Check Voltage Drop

For long cable runs, calculate voltage drop and increase conductor size if necessary.

6. Check Short-Circuit Rating

The conductor and cable construction must withstand the expected fault current for the required duration.

7. Check Mechanical Requirements

Consider whether the cable needs additional protection because of impact, crushing, burial, or industrial conditions.

8. Select Compatible Accessories

Choose the correct:

  • Cable glands
  • Lugs
  • Cleats
  • Terminations
  • Sealing components

Discover More:


Armored Cable Size Chart by Application

Cable Size Range General Application Category
1.5–4 mm² Lighting and small power
6–16 mm² Branch circuits and small feeders
25–50 mm² Medium power distribution
70–120 mm² Large feeders
150–240 mm² High-current distribution
300–400 mm² Heavy industrial power
500–630 mm² Very high-capacity systems

This classification is intended to help organize cable sizes rather than establish mandatory applications.


Common Armored Cable Sizing Mistakes

Choosing Cable Size Only by Amperage

Current capacity is important, but voltage drop and installation conditions can change the required size.

Ignoring Cable Length

A long cable run can produce excessive voltage drop even when ampacity is adequate.

Ignoring Installation Conditions

Buried, enclosed, grouped, tray-mounted, and free-air cables can have different thermal performance.

Confusing Cable Size With Diameter

A 35 mm² conductor size does not mean the finished cable has a 35 mm diameter.

Using the Wrong Gland

The gland must match the cable’s armor and overall dimensions.

Ignoring Short-Circuit Performance

A cable must be capable of withstanding expected fault conditions.

Assuming All Armored Cables Are the Same

SWA, AWA, PVC, XLPE, copper, aluminum, and different core configurations can produce significantly different cable characteristics.


Frequently Asked Questions

What are the common armored cable sizes?

Common armored cable conductor sizes include 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, and 630 mm². Availability varies by cable type, manufacturer, voltage rating, and conductor material.

What size armored cable do I need for 100A?

A 100A load does not automatically correspond to one specific armored cable size. Depending on conductor material, insulation, core configuration, installation method, ambient conditions, grouping, and voltage drop, different sizes may need to be evaluated.

What is the difference between SWA and AWA cable?

SWA uses steel wire armor, providing strong mechanical protection and commonly being used with multicore power cables. AWA uses aluminum wire armor and is commonly selected for certain single-core AC applications where magnetic effects from steel armor need to be avoided.

Is armored cable suitable for underground use?

Some armored cables are designed for underground installation, but not every armored cable is automatically suitable for direct burial. Burial conditions, cable construction, mechanical protection, moisture exposure, soil conditions, and applicable installation requirements must be evaluated.

Does armored cable need a larger size for long distances?

It can. A long cable run can produce greater voltage drop, so a larger conductor may be required even when the original size has sufficient current-carrying capacity. Cable length should therefore be included in the sizing calculation.


Conclusion

An armored cable size chart provides a convenient way to compare common conductor sizes from 1.5 mm² to 630 mm² and understand their general applications. However, cable selection should never be based on conductor size alone.

The correct armored cable depends on load current, conductor material, number of cores, insulation type, installation method, voltage drop, short-circuit conditions, environmental exposure, mechanical protection, and termination requirements.

For accurate cable selection, use the actual manufacturer’s cable data and verify the design against the applicable electrical requirements. Correct sizing helps provide reliable power delivery, effective protection, and safe long-term operation.